Initial Charging Current less than 30.0A.Voltage 14.4V~15.0V at 25°C(77°F) Temp. Coefficient -30mV/°C
Standby Use
No limit on Initial Charging Current Voltage 13.5V~13.8V at 25°C (77°F) Temp. Coefficient -20mV/°C
Capacity affected by Temperature
40°C (104°F) 103%
25°C (77°F) 100%
0°C (32°F) 86%
Self Discharge
Leoch LP series batteries may be stored for up to 9 months at 25° C (77°F) and then a freshening charge is required.For higher temperatures the time interval will be shorter.