UPS12-490MRX

HIGH RATE MAX – VALVE REGULATED LEAD ACID BATTERY


  • 10 year design life @ 25°C
  • Thermally welded case-to-cover bond to eliminate leakage
  • Patented UL Recognized Flame-arresting vents in each cell for safety and long life.
  • Can be operated in upright, side or end mounting orientation.
  • Flame retardant polypropylene case and cover compliant with UL94V-2
  • Absorbent Glass Mat (AGM) technology for efficient gas recombination of up to 99% and freedom from electrolyte maintenance.
  • Patented Long Life Alloy having the lowest calcium levels in the industry – minimizing grid growth, reducing gassing, and extending battery life
  • Proprietary Fixed Orifice Plate Pasting technology applying active materials on both sides of the grid for consistent cell- to-cell performance, higher capacity and uniform grid protection.

APPLICATIONS

Data Centers

Network Operation Centers

Industrial Process Control Facilities

Internet Housing Sites

Semiconductor Manufacturing

Banks and Financial Markets

Power Generation Plants

Hospital and Testing Laboratories

Emergency Response Center

DETAILS

SPECIFICATIONS

Cells Per Unit Voltage Per Unit Weight Watts/Cell @ 15min 1 Min Current to
1.75VPC
Short Circuit Current Resistance
6 12.98v 46.6 kg 490 599 Amps 3160 Amps 3.96 (mOhms)
Operating Temperature Range with temperature compensation Discharge: -40°F (-40°C) to +160°F (71°C)
Charge: -10°F (-23°C) to +140°F (60°C)
Nominal Operating Temperature Range 74°F (23°C) to +80°F (27°C)
Recommended Maximum Charging Current Limit C/5 amperes @ 20hr rate
Float Charging Voltage 13.65 ± 0.15 VDC average per 12V unit
Maximum AC Ripple (Charger) 0.5% RMS or 1.5% P-P of float charge voltage recommended for best results. Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20
Self Discharge Battery can be stored up to 6 months at 77°F (25°C) before a freshening charge is required. Batteries stored at temperatures greater than 77°F (25°C) will require recharge sooner than batteries stored at lower temperatures.
Equalize charge and cycle service voltage 14.40 to 14.80 VDC average per 12V unit @ 77°F (25°C)
Terminal Threaded copper alloy insert terminal to accept 1/4-20 UNC bolt
Terminal Hardware Initial Torque 110 in.-lbs. (12.4 N-m)
SKU: UPS12-490MRX Categories: ,